Laboratuvar
Fault Analysis Lab
Symmetrical-components short-circuit analysis for a source-transformer-cable feeder — pick a fault type, location and resistance, and see the resulting three-phase current and voltage waveforms and phasors, before and after the fault.
Basitçe
Bir güç hattında bir şeyler ters gittiğinde elektriksel olarak ne olacağını simüle eder — bir kablonun toprağa değmesi, ya da iki iletkenin birbirine değmesi gibi. Ne kadar akım akacağını ve yakındaki gerilimin nasıl görüneceğini hesaplar — elektrik mühendislerinin onlarca yıldır elle kullandığı aynı standart yöntemle (simetrik bileşenler) — sadece anında ve kağıt yerine görsel olarak.
Network & fault
01 / inputOne phase to ground — by far the most common fault type in practice (≈70-80%).
Assumed Dyn (delta HV, grounded-star LV) — the standard arrangement for HV/MV distribution transformers, and the reason the grid source doesn't appear at all in the zero-sequence path below.
R, X — left to right.
0.121 kA fault current
Line-ground fault, 40% along the line — equivalent MVA at the largest phase current ≈ 4 MVA.
Reading point
02 / readoutRight at the fault location itself.
IA
0.121 kA
∠-89°
IB
0.000 kA
—
IC
0.000 kA
—
I0 (ground)
0.040 kA
VA
0% nom.
—
VB
171% nom.
∠-149°
VC
171% nom.
∠150°
Min. voltage
0%
Waveform & phasors
Solid = during fault, at At the fault. Dashed = pre-fault.
How this is built: symmetrical- components fault analysis (Fortescue transform + sequence networks) — the same closed- form method used in fault studies and relay-testing tools, not an iterative power flow. Positive- and negative-sequence impedances are treated as equal throughout; the transformer's zero-sequence impedance is assumed equal to its positive-sequence impedance; pre-fault load current is neglected (standard practice for a maximum fault- current study — it's also why MP2, downstream of the fault, reads ~0 current here). The transformer is assumed Dyn, so the grid source never enters the zero-sequence path — only the transformer and its grounding impedance do. Line and cable shunt capacitance is neglected: that is fine for solidly or low-impedance earthed networks, but in isolated or resonant-earthed (Petersen-coil) networks — common in German medium-voltage grids — the earth-fault current is set mainly by that capacitance, so treat single line-to-ground results there as the inductive part only. Per-unit values referred to a fixed 100 MVA system base internally; every result shown is scaled back to real kV/kA, so the choice of base has no effect on any number above.
Explore: IEEE 39-Bus Transient Stability
This lab is a single fault instant on one feeder — see how a fault plays out moment-by-moment across a full multi-machine system instead, including whether generators stay in sync.
Further reading
- J. J. Grainger and W. D. Stevenson Jr., Power System Analysis. New York: McGraw-Hill, 1994. — symmetrical components and fault current calculation
- J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design, 6th ed. Boston: Cengage Learning, 2017. — sequence networks and per-unit fault studies
- IEC 60909-0, Short-circuit currents in three-phase a.c. systems — Part 0: Calculation of currents. Geneva: IEC. — the standard method for short-circuit studies; this tool follows its sequence-network approach but omits its voltage and correction factors