Lab
PD Sensor Signal Chain Lab
A sensor with good saturation headroom is only half the story. What actually reaches your oscilloscope depends on the winding's frequency response and the electronics sitting between it and the scope — explored here for a synthetic 50 Hz + partial-discharge pulse, continuing where the core-geometry trade-off in Flux Concentrator Lab leaves off.
A trade-off you don't see from geometry alone
A published R-L bypass network strongly rejects the 50 Hz operating current that would otherwise swamp the measurement — the chart below reproduces its published 73 dB of attenuation at 50 Hz exactly. But the same filter also reshapes the much faster PD pulse it's meant to pass through: toggle it below and watch the pulse's ringing roughly double. Good 50 Hz rejection and a clean PD waveform are not automatically the same goal.
Output filter (Fritsch R-L bypass)
Secondary turns
PD pulse rise time
50 Hz operating current
PD peak at scope
0.622 V
Rise time
0.71 ns
Overshoot / ringing
3.7 %
50 Hz attenuation (filter)
-73.4 dB
Frequency response, Z_T(f)
The sensor's own transfer impedance (Fritsch & Wolter, IEEE TIM 2022) rises from 50 Hz up to a plateau; the output filter (orange) suppresses the low end further while converging to the same plateau at high frequency — the two always meet, by construction.
Plain 50 Ω burden With R-L bypass
Reconstructed PD pulse, v_out(t)
A double-exponential PD current pulse through the whole chain, bare vs. with the output filter. Redraws when you fire a pulse with the current controls.
Bare With filter
What the real papers actually measured
The 50 Hz attenuation row below is the published Fritsch & Wolter (POWERCON 2022) design example, reproduced exactly by the engine above. The THD-threshold rows are Zimmer et al. (2026) Table 3 — experimental data, not computed by this tool.
| Gap / geometry | THD = 1% threshold | THD = 5% threshold |
|---|---|---|
| HFCT, 0.0 mm gap | 16 A | 23 A |
| HFCT, 1.1 mm gap | 184 A | 219 A |
| HFCT, 6.5 mm gap | 384 A | 440 A |
| MFCS (half-core) | >450 A — threshold not reached within the tested range (censored, not a measured value) | |
How this is built, and its real limits: this is a linear, unsaturated small-signal model — it cannot produce harmonic distortion by construction, which is why THD is never one of the numbers above. The transfer-impedance model and the output filter are combined as two cascaded linear blocks (multiplying their transfer functions), not solved as one unified circuit with the bypass as a third parallel branch — a reasonable first approximation, not a lab-accurate voltage prediction. The material constant (μ_r = 800) is a Fair-Rite 43 manufacturer reference value used for validating the conventional closed-HFCT model, not a measured MFCS material, and the magnetic-circuit diagnostic above uses the conventional small-gap HFCT geometry, never the half-ring MFCS — per Flux Concentrator Lab's own rule, the open MFCS core must not be treated as an equivalent air gap. Neither model includes winding self-capacitance, so the combined response plateaus rather than resonates at high frequency.
Explore: Flux Concentrator Core Geometry Lab
The upstream half of this story — how much core material a PD sensor actually needs, and the sensitivity it trades away by opening the magnetic path.
Further reading
- M. Fritsch and M. Wolter, “High-frequency current transformer design and construction guide,” IEEE Transactions on Instrumentation and Measurement, vol. 71, pp. 1–9, 2022. — HFCT transfer impedance and construction
- M. Fritsch and M. Wolter, “An alternative method for dealing with saturation in high-frequency current transformers,” in Proc. IEEE International Conference on Power Systems Technology (POWERCON), 2022, pp. 1–5. — the published output-filter design example reproduced by this lab
- B. Zimmer, F. Jenau, D. Ripka and N. Porath, “A sensor concept for direction-selective monitoring of partial discharges in medium-voltage switchgears,” Sensors, vol. 26, art. 2672, 2026. — the measured THD thresholds shown in the comparison table
- Reuses the core/winding model from the Flux Concentrator Core Geometry Lab — see that tool for the geometry-side sources.