Lesson 10 of 10
Symmetrical Components & Fault Calculation
A three-phase fault is easy to calculate: the network stays balanced, so one per-phase circuit is enough. But most real faults involve only one or two phases, and then the network is no longer balanced. In 1918 Charles Fortescue showed how to turn one unbalanced problem into three balanced ones. That method — symmetrical components — is still how every short-circuit study and every Fault Analysis Lab result on this platform is calculated.
The idea: three balanced sets
Any set of three unbalanced phasors can be written as the sum of three balanced sets, each easy to analyse on its own:
- Positive sequence (1)
- Three equal phasors 120° apart in the normal rotation a–b–c. A healthy, balanced system contains only this component.
- Negative sequence (2)
- Three equal phasors 120° apart in the reverse rotation a–c–b. It appears whenever the system is unbalanced and heats rotating machines.
- Zero sequence (0)
- Three equal phasors exactly in phase. It can only flow if there is a return path through earth or a neutral conductor.
Using the operator a = 1∠120° (so a² = 1∠240°), the phase voltages are rebuilt from the sequence components, and the components are extracted from the phase voltages:
From sequence to phase quantities
From phase to sequence quantities
The same relations hold for currents.
Sequence networks
The trick works because, in a network that is itself symmetrical, each sequence current only produces voltage drops of the same sequence. Each component therefore sees its own impedance network:
- Positive-sequence Z₁
- The normal per-phase impedances used in power flow — with generators represented by their subtransient reactance X″d and internal voltage.
- Negative-sequence Z₂
- For lines, cables and transformers equal to Z₁. For rotating machines somewhat different, but of the same order as X″d. There are no sources in this network.
- Zero-sequence Z₀
- Depends strongly on earthing and transformer connections. A delta winding blocks zero-sequence current from passing through; an unearthed neutral blocks it entirely; a neutral earthed through impedance Zₙ adds 3Zₙ to the path.
Why Z₀ is the interesting one
Connecting the networks for each fault type
Each fault type imposes conditions at the fault point that tell you how to connect the three networks. With Vf the pre-fault voltage and Zf the fault impedance:
- Three-phase (3φ)
- Only the positive-sequence network is involved: I_f = V_f / Z₁.
- Single line-to-ground (SLG)
- All three networks in series: I₁ = I₂ = I₀ = V_f / (Z₁ + Z₂ + Z₀ + 3Z_f), and the fault current is I_a = 3I₀.
- Line-to-line (LL)
- Positive and negative networks in parallel, no zero sequence: I₁ = −I₂ = V_f / (Z₁ + Z₂), giving a phase current of magnitude √3·|I₁|.
- Double line-to-ground (LLG)
- The positive network in series with the negative and zero networks in parallel: I₁ = V_f / (Z₁ + Z₂ ∥ (Z₀ + 3Z_f)).
A worked example
Take Vf = 1.0 p.u. at a bus close to a solidly earthed transformer, with Z1 = Z2 = j0.20 p.u. and Z0 = j0.10 p.u., and a bolted fault (Zf = 0):
Three-phase fault
Single line-to-ground fault
Here the earth fault is larger than the three-phase fault — the case flagged in the faults lesson. Earth the same transformer through a resistor or reactor so that Z0 rises to j0.60 p.u., and the earth-fault current falls to 3 / 1.0 = 3.0 p.u. This is exactly why network operators choose an earthing method: it sets the size of the most common fault.
How it is done in practice
Real short-circuit studies follow a standard so that results are comparable. In Europe that is IEC 60909, which replaces detailed pre-fault load flow with an equivalent voltage source cUn/√3 at the fault location — the voltage factor c (typically 1.1 for maximum currents in high-voltage networks) covers the spread of real operating voltages — and then uses exactly the sequence networks described here to find the initial symmetrical short-circuit current, the peak current and the breaking current.
Key takeaways
- Any unbalanced three-phase set is the sum of balanced positive-, negative- and zero-sequence sets.
- In a symmetrical network each sequence has its own independent impedance network.
- Zero-sequence impedance depends on earthing and transformer connections and largely decides earth-fault current.
- Each fault type connects the sequence networks in a specific way — in series for SLG, positive and negative in parallel for LL.
- Close to solidly earthed transformers a single line-to-ground fault can exceed the three-phase fault current.
Further reading
- C. L. Fortescue, “Method of symmetrical co-ordinates applied to the solution of polyphase networks,” Transactions of the AIEE, vol. 37, no. 2, pp. 1027–1140, Jul. 1918. — the original paper that introduced the method
- J. J. Grainger and W. D. Stevenson Jr., Power System Analysis. New York: McGraw-Hill, 1994. — symmetrical components and unsymmetrical faults, with many worked examples
- J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design, 6th ed. Boston: Cengage Learning, 2017. — sequence networks of lines, transformers and machines
- IEC 60909-0, Short-circuit currents in three-phase a.c. systems — Part 0: Calculation of currents. Geneva: IEC. — the standard procedure used for short-circuit studies in European practice
Fault Analysis Lab
Switch from a three-phase to a single-line-to-ground fault and watch the zero-sequence current appear.